Installation and Operating Instructions
SDC 306 1316BED036-11B-E Date 06/09
- 13 -
7 C
OMMISSIONING
Commission your control unit in the following sequence:
?
Are the collector and storage cylinder sensors
correctly mounted
?
Has the correct sensor type been selected
(PT1000)?
Yes No
Select and install the correct sensor
?
Is the power cable for the pump connected correctly
to the pump and the control unit?
Yes No
Connect the cables correctly
§
If the pump is powered directly via a mains cable:
does the pump work?
Yes
Unplug the mains plug
No
Unplug the mains plug
Test the pump cable,
test the pump
Reconnect the pump to the control unit
?
Are the sensor cables for the collector and storage
cylinder sensors correctly connected to the relevant
control unit terminals?
Yes No
Connect sensors correctly
§
With the mains supply switched off, connect the
control unit and then switch on the mains supply (e.g.
via a safety fuse):
?
Does data appear on the display
Yes No
Test the fuse on the device
Check the fuse protection on the mains
Using the programming menu, set the correct time.
On the basic settings menu, enter the activation code
(preset: 0000).
On the basic settings menu, enter your system
diagram.
On the basic settings menu, change the parameters
according to the required function.
Enter the parameters (e.g. time window, hysteresis,
etc.) on the program menu.
?
Does the system run as it should?
Yes No
Check the parameters
Rectify fault as described in section 12
Control unit is ready for use.